8
Installation
Braking resistors
Product Manual – MOVIDRIVE
®
system
247
8.8 Braking resistors
The supply cables to the braking resistors carry a high pulsed DC voltage during nom-
inal operation.
DANGER
Dangerous pulsed DC voltage of up to 970V.
Severe or fatal injuries from electric shock.
To prevent electric shocks:
Disconnect the application inverter from the power supply and wait 10 minutes
before working on a braking resistor or its supply cables.
Never operate the application inverter without touch guards and installed closing
covers.
Braking resistors get very hot during operation.
WARNING
The surfaces of the braking resistors will reach temperatures of up to 250°C when
the braking resistors are loaded with the nominal power.
Severe burns.
To prevent burns:
Do not touch any hot braking resistor.
Select a suitable installation location for the braking resistors such as the control
cabinet roof.
28487486/EN – 02/2019
8

Table of Contents

Other manuals for SEW-Eurodrive MOVIDRIVE system

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SEW-Eurodrive MOVIDRIVE system and is the answer not in the manual?

SEW-Eurodrive MOVIDRIVE system Specifications

General IconGeneral
CategoryInverter
SeriesMOVIDRIVE system
Output Voltage0 - Input Voltage
Protection ClassIP20, IP65 (depending on model)
TypeFrequency Inverter
Output CurrentVaries by model
Control MethodSensorless vector control, V/f control
Communication InterfacesCANopen
SafetySafe Torque Off (STO), Safe Stop 1 (SS1)
Input Voltage200-240V AC, 380-480V AC, 500-600V AC