Mechanical installation
Minimum clearance
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
46
5.3.1 Vertical installation
The following figure shows the required minimum clearance of the device:
27021607564391563
The following table lists the minimum clearances:
Clearance Function Size
A: Above Space for optimum heat convection
The cooling fins must not be located in a
closed hollow space.
≥ 200mm
B: To the side on the right Space for connection cables, plug connect-
ors, mounted elements and actuator ele-
ments, e.g. maintenance switch
See dimension drawings in
chapter "Technical
data"(→2164)
• Without connection cable or
mounting elements: ≥ 30mm
• With interface box: ≥ 200mm
• With connection for device
supply: ≥ 250mm
C: Device cover Space for display elements, diagnostics
elements and actuator elements, such as
service unit
≥ 150mm
D: Below Space for connection cables, plug connect-
ors
See dimension drawings in
chapter "Technical
data"(→2164)
E: To the side on the left Space for optimum heat convection ≥ 30mm
F: Behind the cooling fins Space for optimum heat convection ≥ 15mm
26596598/EN – 10/2020