Minimum clearance
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
47
5.3.2 Horizontal installation
The following figure shows the minimum clearance of the device:
45035996737809931
The following table lists the minimum clearances:
Clearance Function Size
A: Device cover Space for display elements, diagnostics
elements and actuator elements, such as
service unit
≥ 150mm
B: To the side on the right Space for connection cables, plug connect-
ors, mounted elements and actuator ele-
ments, e.g. maintenance switch
See dimension drawings in
chapter "Technical
data"(→2164)
• Without connection cable or
mounting elements: ≥ 30mm
• With interface box: ≥ 200mm
• With connection for device
supply: ≥ 250mm
C: To the front Space for connection cables, plug connect-
ors
See dimension drawings in
chapter "Technical
data"(→2164)
D: Below the cooling fins Space for optimum heat convection
The cooling fins must not be located in a
closed hollow space.
≥ 15mm
E: To the side on the left Space for optimum heat convection ≥ 30mm
F: To the back Space for optimum heat convection ≥ 30mm