Electrical installation
Cable routing
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
60
6.6 Cable routing
Observe the following when routing the cables:
Use suitable cables to connect power supply and communication. For more infor-
mation on connection descriptions, refer to chapter "Electrical connec-
tions"(→271).
Route power cables and signal cables in separate cable ducts.
Maintain the greatest possible distance between power cables and signal cables.
Avoid using long cables running parallel to one another.
For further information on EMC compliant installation, refer to the following documen-
tation: "Drive Engineering Practical Implementation, Electromagnetic Compatibility
(EMC) in Drive Engineering".
6.7 Shielding
Use shielded power and electronics cables.
Connect the shield and make sure it is grounded over a wide area at both ends.
When using cables with multiple shielding, also make sure that the inner shields
are grounded over a wide area at both ends.
Use EMC-capable plug connectors.
For external bus connections, refer to the bus-specific installation instructions.
6.8 Protective measures against electrical hazards
6.8.1 Overview
Preventive measures according to IEC60364‑4‑41
Stationary use Mobile application
Direct power supply
Ground connection
24171709707
26596598/EN – 10/2020