6
Electrical installation
Electrical connections
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
81
Device power Coding of the connections
11kW
15kW
22kW
DC24V supply
The internal components can be supplied with DC 24V either from the device or via
an external DC 24V backup voltage.
To use the internal DC 24V supply, you must jumper the following contacts:
• [c].1 and [c].3
• [c].5 and [c].7
INFORMATION
If you use an external DC 24 V backup voltage, do not connect contacts [c].3 and
[c].7.
To use an external DC 24V backup voltage, connect it to the following contacts:
• [c].1
• [c].5
26596598/EN – 10/2020