14 Annex
14.1 Notes on PROFINET
14.1.1 Basic information on PROFINET
SICK recommends familiarizing yourself with the basic information described in the
planning guidelines and commissioning guidelines of the PI user organization
(PROFIBUS & PROFINET International, homepage: www.profinet.com).
These guidelines can be found in the "Downloads" area at:
www.profibus.com
14.1.2 General notes on PROFINET wiring
The signal lines must be wrapped in pairs (twisted pairs) and comply with at least CAT5
in line with ISO/IEC 11801 Edition 2.0. Class D. The signal lines must also be shielded
and grounded.
SICK recommends using components certified by PROFINET.
More detailed information can be found in the “PROFINET Cabling and Interconnection
Technology” Installation Guide.
You can find the document in the “Downloads” area at:
www.profibus.com
14.1.3 PROFINET Conformance Class
The device complies with PROFINET Conformance Class B (CC-B) and supports the
properties defined within.
Further information on the PROFINET Conformance Classes can be found in the docu‐
ment of the PI user organization (PROFIBUS and PROFINET International).
You can find the document in the “Downloads” area at:
www.profibus.com
14.1.4 General requirements on a switch suitable for PROFINET applications
For PROFINET Conformance Class B and C (CC-B / CC-C), a PROFINET-certified switch
which can be configured as a PROFINET device must be used.
For further information, refer to the commissioning guidelines of the PI “Installation
Guideline PROFINET Part 2: Network Components”.
You can find the document in the “Downloads” area under:
www.profibus.com
14.1.5 Notes on installing the SICK bar code scanner into a PROFINET network
For 1-port devices, these include:
LLDP (neighborhood detection)
1)
I&M 0-4 (device identification)
1)
Device exchange by topology check
1)
16 bit digital “status word” for reading gate result
16 bit digital “control word” for controlling the device via PLC
Heartbeat (for checking communication)
GSD file for configuring the device using modules via the PLC
1)
1)
Properties of the CC-B
ANNEX 14
8019588/129Z/2019-02-07 | SICK O P E R A T I N G I N S T R U C T I O N S | CLV63x, CLV64x, CLV65x
97
Subject to change without notice

Table of Contents

Other manuals for SICK CLV63 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK CLV63 Series and is the answer not in the manual?

SICK CLV63 Series Specifications

General IconGeneral
BrandSICK
ModelCLV63 Series
CategoryBarcode Reader
LanguageEnglish

Related product manuals