6.3.2 Wiring the outputs
DANGER
Safety-oriented devices must be suitable for safety-related signals!
A functional interruption of safety outputs leads to the loss of the safety functions,
meaning there is the risk of serious injury.
Do not connect any loads that exceed the nominal values of the safety outputs.
Wire the UE410-SD so that 24 V DC signals cannot contact the safety outputs.
Connect the GND lines of the voltage supply to ground in order that the devices do
not switch on if the safety output line is at the ground potential.
The UE410-SD, the sensors and the connected protective devices must be con‐
nected to the same GND connection.
Use suitable components and devices that meet all applicable regulations and
standards.
NOTE
In or
der to detect errors in safety outputs Q1/Q2, the outputs are tested periodically.
6.3.3 Connection layouts
The components must be wired as shown in the figures.
Figure 12: Connection layout for operating mode with one sensor pair
1
Selection of the operating mode
2
Configuration of output Q3
3
Reset pushbutton
ELECTRICAL INSTALLATION 6
8021417/2018-01-17 | SICK O P E R A T I N G I N S T R U C T I O N S | UE410 Safeguard Detector Box
25
Subject to change without notice