13 Technical data
13.1 Data sheet for the safety system
Table 7: Safeguard Detector Box UE410 safety system safety technology parameters
Safety integrity level
1)
SIL2 (IEC 61508)
SIL claim limit
1)
SILCL2 (EN 62061)
Category Sensors: category 3
S
afety evaluation module: category 4
Overall subsystem (sensors + safety evaluation module):
category 3
(EN ISO 13849-1)
Performance level
1)
PL d (EN ISO 13849-1)
PFH
D
1.5 × 10
-9
DC
a
vg
80% (low) (EN ISO 13849-1)
MTTF
D
(
for each channel) 63 years (high) (EN ISO 13849-1)
CCF Fulfilled (EN ISO 13849-1)
T
M
(mis
sion time) 20 years (EN ISO 13849-1)
1)
For detailed information on the safety configuration of your machine/system, please consult your SICK
sub
sidiary.
Table 8: Response time of the overall safety system
Response time of the overall safety
s
ystem (sensors and safety evalua‐
tion module)
Max. 160 ms
13.2 Data sheet for Safeguard Detector sensor
Table 9: General sensor data
10 Hz variant
Connection type Male connector, M8, 3-pin
Maximum length of cable between
sensor and s
afety evaluation module
10 m
Detection area
1)
30 ... 100 mm
Light spot diameter / distance 7 mm/50 mm
Type of light Visible red light
Wavelength 650 nm
Voltage supply Over UE410-SD (U
OUT
)
Output current I
ma
x
100 mA
Pulse rate 10 Hz
Max. switching sequence
2)
10 Hz
Max. response time
3)
see table 8, page 38
Enclosure rating IP67 (EN 60529)
Protection class III
Circuit protection
4)
A, C, D
13 TECHNICAL DATA
38
O P E R A T I N G I N S T R U C T I O N S | UE410 Safeguard Detector Box 8021417/2018-01-17 | SICK
Subject to change without notice