EasyManua.ls Logo

Siemens 1PH813 - Maintenance Intervals; General Inspection Guidelines

Siemens 1PH813
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
9.1 Inspection and maintenance
Synchronous/induction motors 1PH813
Operating Instructions, 04/2009, 610.48000.22
65
9.1.2 Maintenance intervals
General
Careful and regular maintenance, inspections, and overhauls are essential for detecting and
eliminating faults in good time before they can cause any damage.
NOTICE
Inspection if there are faults or unusual conditions
Unusual conditions or faults that place undue electrical or mechanical stress on the three-
phase motor (e.g. overload, short-circuit) can cause consequential damage to the machine.
If faults or any unusual conditions occur (e.g overload or short-circuit), the machine must be
inspected immediately.
Measures, inspection/maintenance intervals
Operating conditions and characteristics can vary widely. For this reason, only general
maintenance intervals can be specified here.
Maintenance intervals should, therefore, be scheduled to suit the local conditions (fouling,
switching frequency, load, etc.).
Perform the following measures after the operation time or the interval specified in the
following table elapses.
Table 9- 1 Measures after operating times or intervals
Measures Operating tines and intervals
Initial inspection After 500 operating hours, after 6 months at the latest
General inspection
Without radial shaft sealing rings
With radial shaft sealing rings
Approx. every 8000 operating hours, after 2 years at the latest
Approx. every 5000 operating hours, after 2 years at the latest
Replace the bearings Note the recommended bearing replacement intervals (see "Bearing
replacement intervals")
Replace the radial shaft sealing rings Approximately every 5000 operating hours
Clean the fan (forced ventilation) Depending on local degree of pollution
Cooling water system (water cooling) Maintenance free (provided that the required cooling water quality is ensured)
9.1.3 General inspection guidelines
When inspecting a motor, you do not generally need to dismantle it. The motor only be
dismantled if the bearings need to be replaced.

Table of Contents