Commissioning
5.4 Basic commissioning
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
91
To initiate motor data identification and optimization of the motor control, proceed as follows:
Open by double-clicking on the control panel in
STARTER.
Assume master control for the converter.
Set the "Enable signals"
Switch on the motor.
The converter starts the motor data identification.
This measurement can take several minutes.
After the measurement, the converter switches off
the motor.
Relinquish the master control after the motor data
identification.
Click the Save (RAM to ROM) button.
You have now completed motor data identification.
Self-optimization of the closed-loop control
If you have also selected a rotating measurement with self-optimization of the speed control
in addition to the motor data identification, then you must switch on the motor again as
described above and wait for the optimization run to be completed.