Commissioning
5.4 Basic commissioning
Inverter with CU230P-2 Control Units
90 Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
5.4.2.5
Identifying motor data
Preconditions
In the basic commissioning, you have selected the motor identification (MOT ID). In this
case, after the basic commissioning has been completed, the converter issues the alarm
A07991.
The motor has cooled down to the ambient temperature.
If the motor is too hot, the motor data identification will provide incorrect values and the
closed-loop speed control will become unstable.
DANGER
Risk of injury or material damage as a result of machine movements when switching on the
motor
Switching on the motor for identification purposes may result in hazardous machine
movements.
Secure dangerous machine parts before starting motor data identification:
Before switching on, check that no parts are loose on the machine or can be spun out.
Before switching on, ensure that nobody is working on the machine or located within its
working area.
Secure the machine's work area against unintended access.
Lower hanging/suspended loads to the floor.

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals