Parameter  Parameter  Edit  Value range  Resolution  Factory setting  Password level  Password level 
number      Min.  Max.      reading from level  writing from level 
600  Power setting               
654  Analog input (feedback potentiometer ASZxx.3x required) 
0 = 3-position step input 
1 = 0...10 V 
2 = 0...135  
3 = 0...20 mA 
4 = 4...20 mA with lockout at I <4 mA 
5 = 4...20 mA 
Edit 0  5  1  1  SO  SO 
            
700  Error history               
701 Current error: 
00: Error code 
01: Startup meter reading 
02: MMI phase 
03: Power value 
Read only   
2 
0 
--- 
0% 
 
255 
999999 
--- 
100% 
 
1 
1 
--- 
1 
--- Service --- 
702  Error history former 1: 
00: Error code 
01: Startup meter reading 
02: MMI phase 
03: Power value 
Read only   
2 
0 
--- 
0% 
 
255 
999999 
--- 
100% 
 
1 
1 
--- 
1 
--- Service
  --- 
•         
 
 
•         
 
 
•         
 
 
711  Error history former 10: 
00: Error code 
01: Startup meter reading 
02: MMI phase 
03: Power value 
Read only   
2 
0 
--- 
0% 
 
255 
999999 
--- 
100% 
 
1 
1 
--- 
1 
--- Service
  --- 
            
900  Process data               
936  Normalized speed  Read only  0%  100%  0.01%  ---  Service  --- 
951  Mains voltage  Read only  0 V  LME73.000A1: 175 V 
LME73.000A2: 350 V 
1 V  --- 
Service
 
--- 
954  Flame intensity  Read only  0%  100%  1%  --- 
Service
 
---