70/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  12 PME71.901...  29.11.2011 
12.5 Parameter list PME71.901... (AZL2...)  
 
Value range Parameter 
number 
Parameter  Edit 
Min.  Max. 
Resolution  Factory setting  Password level 
reading from level 
Password level 
writing from level 
000  Internal parameter               
41  Heating engineer's password (4 characters)  Edit  xxxx  xxxx  ---  ---  ---  OEM 
42  OEM's password (5 characters)  Edit  xxxxx  xxxxx  ---  ---  ---  OEM 
60 Backup/restore  Edit Restore Backup --- ---  ---  SO 
           
100  General               
102  Identification date  Read only  ---  ---  ---  ---  Info  --- 
103  Identification number  Read only  0  9999  1  0  Info  --- 
113 Burner identification  Edit x  xxxxxxxx 1  burnErId  Info  SO 
123  Min. power control step  Edit  1%  10%  0.1  2  SO  SO 
140  Mode display of display and operating unit AZL2... 
1 = standard (program phase) 
2 = flame 1 (QRA.../ION) 
3 = flame 2 (QRB.../QRC...)  not used 
4 = active power (power value) 
Edit 1  4  1  4  SO  SO 
164  Number of startups resettable  Resettable  0  999999  1  0  Info  Info 
166  Total number of startups  Read only  0  999999  1  0  Info  --- 
170.00  Switching cycles actuator relay K12  Read only  0  999999  1  0  Info  --- 
170.01  Switching cycles actuator relay K11  Read only  0  999999  1  0  Info  --- 
170.02  Switching cycles actuator relay contact 2  Read only  0  999999  1  0  Info  --- 
170.03  Switching cycles actuator relay contact 1  Read only  0  999999  1  0  Info  --- 
171  Max. switching cycles actuator relay  Read only  0  999999  1  0  Info  ---