33/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  4 Technical data  29.11.2011 
 
4.7  Signal cable AGV50...  
4.7.1 AZL2...  BCI 
 
Signal cable 
Color white 
Unshielded 
Conductor 4 x 0.141 mm² 
With jack RJ11 
Cable length 
- AGV50.100 
 
1 m 
Supplier (alternative)  Recommendation: 
Hütter  
http://www.hkt-
netzwerktechnik.at/index.htm 
Location  Under the burner hood (arrangements for 
SKII EN60730-1 additionally required) 
 
4.8  Dummy plug for RJ11 
 
Dummy plug 
For 6 pin modular plug (RJ11) 
Supplier Recommendation: 
Molex 
Order no.: 085 999 3256 
 
4.9 Environmental conditions 
 
Storage 
DIN EN 60721-3-1 
Climatic conditions  Class 1K3 
Mechanical conditions  Class 1M2 
Temperature range  -40...+70 °C 
Humidity <95% r.h. 
Transport 
DIN EN 60721-3-2 
Climatic conditions  Class 2K3 
Mechanical conditions  Class 2M2 
Temperature range  -40...+70 °C 
Humidity <95% r.h. 
Operation 
DIN EN 60721-3-3 
Climatic conditions  Class 3K3 
Mechanical conditions  Class 3M2 
Temperature range  -40...+60 °C 
Humidity <95% r.h. 
 
 
Warning! 
Condensation, formation of ice and ingress of water are not permitted!  
If not observed, there is a risk of impairment of safety functions and of 
electric shock hazard.