163/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  21 Multistage or modulating mode  29.11.2011 
 
21  Multistage or modulating mode 
 
21.1 Relevant parameters 
 
Parameter  Meaning 
123  Minimum power control step 
259  Opening time of actuator (timeout) 
260  Closing time of actuator (timeout) 
654  Analog input (feedback potentiometer ASZxx.3x required) 
0 = 3-position step input 
1 = DC 0...10 V 
2 = 0...135  
3 = 0...20 mA 
4 = 4...20 mA with lockout at I <4 mA (AZL2…: Loc: 60) 
5 = 4...20 mA 
 
21.1.1 Connection diagram for feedback potentiometer 
ASZ12.33 
 
 
Note: 
The connection diagram shown is merely an example which must be verified in the 
individual case depending on the application! 
 
PME7... 
X66
ASZ12.33
Termin a l X66
on the LME7...
Type
SQNx1...
SQMx1...
SQNx0...
SQMx0...
2
(Signal)
3
(GND)
a
b
c
a
b
c
a
b
c
a
b
c
Terminal potentiometer
(1 kOhm conductive 
plastik 90°) ASZxx30
Rotation 
direction
Clockwise
Counter-
clockwise
X
X
X
X
---
---
---
---
ab
c
7105d39e/1009
 
Figure 84: Connection diagram for feedback potentiometer ASZ12.33