Infrastructure & Cities Sector  27 PWM settings  29.11.2011 
 
 
Checking the ignition load 
 
  To check the ignition load speed, set the required worst-case conditions close to 
the overvoltage limit 
  Start the burner and check the speed, the volumetric air flow or air pressure by 
taking appropriate measures while ensuring compliance with the relevant 
standards (e.g. EN 676) in the ignition phase (P38, P40 or P44) 
  If the worst-case requirements are not satisfied, change safety parameter 675.01 
accordingly  
 
On successful completion of the test, reset parameter 559 to control as described 
above (setting value = 1). 
 
 
Note: 
To store the settings in the PME... program module, a manual backup is required. 
Also see chapter Manual backup. 
 
27.4.5  Matching the working points “Speeds for low-fire (P1), 
ignition load (P0) and high-fire (P2) for the heating 
engineer to the application 
 
Prerequisites 
 
  Initial settings of the basic PWM parameters on the OEM level are made 
  Unit is wired up in accordance with the proposed application 
  Mains voltage is available 
  Safety loop is closed 
  There is no heat request, unit is in standby (OFF)