93/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  15 PME73.810...  29.11.2011 
 
15 PME73.810...  
15.1 Program sequence PME73.810...  
 For connection diagram fuel train (G) without valve proving 
 For connection diagram fuel train (G) with valve proving 
 For connection diagram actuator application example 1 
710 5d 74e/ 1111
M
Z
V1
V2a
AL
K1X2-02 Pin 3
Actuator position
High-fire
Cam V2
Ignition load / low-fire
CLOSE
R
LR-AUF
LR-ZU
LP
Pmin
P LT
ION / QRA
Not active
X3-04 Pin 5
Relay
contact
Function / inputs
Display and operation unit parameter number
LED permanent
LED flashing
tw          t11    t10       t12    t3    t3n      t4                   t8        td4   td1  td3   td2
Standby           Startup          Operation         Shutdown   Valve proving
                               setzung    If parameter
                              P241 =1 (ON)
Can be 
parameterized
t1        
TSA
259        225    260 226 257      234
Relay
contact
Function / outputs
SK
X3-04 Pin 1
X5-03 Pin 1
X5-03 Pin 3
X65 Pin 1
X5-03 Pin 2
X65 Pin 1
X3-02 Pin 1
X5-01 Pin 2
X2-02 Pin 4
X9-04 Pin 2
K1X6-03 Pin 3
K4X2-01 Pin 3
K5X4-02 Pin 3
K7X7-04 Pin 4
X7-01 Pin 3
K2/1X2-03 Pin 3
Phase number
21 22  24 22  30  30 36  38  40  42  44  72 74 10  80 81 82 83 
oP: xx (Istleistung in %) 
74 
224       
t11
POC
POC
240 240 240 240 240 240 242 243 244 245
t11 t12
SV
V2
K9X7-02 Pin 3
SA-KL
K12X2-09 Pin 2
SA-NL
K11X2-09 Pin 3
SA-Z
X2-09 Pin 1
SA-R
X2-09 Pin 4
Input from cam V2
X2-09 Pin 8
Output from cam V2
X2-09 Pin 7 K2/2
*) *) *) *)*)
*1
*2
 
Figure 38: Program sequence PME73.810... for connection diagram fuel train (G) 
*) During the actuator running phases, the actuator feedback signal must be OFF first, then ON. 
*1  Valve proving when P241 = 1 after mains ON, lockout or P234 (postpurge time t8) = 0 seconds 
*2  Valve proving when P241 = 1 and P234 (postpurge time t8) >0 seconds