236/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  27 PWM settings  29.11.2011 
 
27.5 Overview of PWM fan parameters  
(value range refers to PME71.901)  
 
Parameter-  Designation  Value range  Step size *)  Conditions 
number 
 
Min.  Max. 
   
403.00  Fan speed: Ignition load speed (P0)  800  9000  10 rpm  Factory setting 3000 rpm 
403.01  Fan speed: Low-fire speed (P1)  800  9000  10 rpm  Factory setting 1200 rpm 
403.02  Fan speed: High-fire speed (P2)  800  9000  10 rpm  Factory setting 5700 rpm 
503.00 
No-flame speeds PWM fan: Standby 
speed 
0  9000  10 rpm  0 up to max. speed 
503.01  No-flame speeds PWM fan: Purge speed  800  9000  10 rpm  < max. speed 
516.00  Limit speed ignition load P0: Min. limit  800  9000  10 rpm  P1min < P0min < P1max 
516.01  Limit speed ignition load P0: Max. limit  800  9000  10 rpm  P0max < P1max 
517.00  Limit speed low-fire P1: Min. limit  800  9000  10 rpm  --- 
517.01  Limit speed low-fire P1: Max. limit  800  9000  10 rpm  P1max < P2min 
518.00  Limit speed high-fire P2: Min. limit  800  9000  10 rpm  P2min > P1max 
518.01  Limit speed high-fire P2: Max. limit  800  9000  10 rpm  P2max > P2 min 
519  Max. speed fan  3000  9000  10 rpm  Factory setting 5830 rpm 
522  Ramp-up low-fire  high-fire  2.058  74.970  0.294 s  Factory setting approx. 15 s 
523  Ramp-down high-fire  low-fire  2.058  74.970  0.294 s  Factory setting approx. 15 s 
559 
PWM mode 
0 = open loop control 
1 = PID control 
2 = safety mode (PWM limits) 
0  2  1  Factory setting 1 (control) 
560 
Mode: Pneumatic ratio control 
0 = OFF 
1 = PWM fan 
2 = air damper actuator 
0  2  1  Factory setting 1 (PWM fan) 
644  Number of pulses per revolution  2  5  1  Factory setting 3 (Hall pulses/rev) 
646  Settling time for speed assessment  1.029  2.058  0.147 s  Factory setting 2.1 seconds 
650.00  Speed tolerance band: Speed shutdown  1  5  1%  Factory setting 1% 
650.01 
Speed tolerance band quick speed 
shutdown 
1  10  1%  Factory setting 3% 
658.00  PWM values fan: Start PWM  1  100  1%  Factory setting 25% 
658.01  PWM values fan: Min. PWM  0  20  1%  Factory setting 0% 
658.02  PWM values fan: Max. PWM  80  100  1%  Factory setting 100% 
659.00  Ramp time of fan: Min. low-fire to high-fire  0  74.970  0.294 s  Factory setting 2.058 seconds 
659.01 
Ramp time of fan: Max. low-fire to high-
fire 
0  74.970  0.294 s  Factory setting 74.970 seconds 
659.02  Ramp time of fan: Min. high-fire to low-fire  0  74.970  0.294 s  Factory setting 2.058 seconds 
659.03 
Ramp time of fan: Max. high-fire to low-
fire  
0  74.970  0.294 s  Factory setting 74.970 seconds 
660  Tolerance time speed deviation  0  37.485  0.147 s  Factory setting 4.998 seconds 
674  Neutral band (permitted control offset)  0  255  1 rpm  Factory setting 40 rpm 
675.00  PWM: Min. PWM with prepurging, SEC  0  100  1%  Factory setting 86% 
675.01  PWM: Max. PWM with ignition load, SEC  0  100  1%  Factory setting 34% 
676  Gain factor speed control  0  255  1  Factory setting 112