191/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  23 Operation via AZL2…  29.11.2011 
 
 
 
reset
 
 
 
 
 
Press 
reset
 to activate the restore process. 
 
Display shows run 
 
<3 s 
 
After approx. 3 seconds (depending on the duration of the 
program sequence), the displays shows rSt End and 
signaled the end of the restore process. 
 
Display: rSt End 
 
It will now be displayed for 2 minutes, or can be finished by pressing the 
reset
 button 
 
 
 
 
<2 
min 
 
or 
 
reset
 
 
Display shows OFF when the restore process is finished. 
 
 
Note: 
During the restore process, all settings and parameters are written from the program module to 
the basic unit’s onboard memory. In the process, it is possible that previous program 
sequences, parameters and settings in the onboard memory will be overwritten! 
 
 
Warning! 
On first startup or after exchange of the program module, the sequence of functions and 
parameter settings must be checked upon completion of the restore process. If this is not 
observed, there is a risk of loss of safety functions. 
 
 See chapter Operation via AZL2.../first startup, restore 
 See chapter Operation via internal LED/first startup, restore