25/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  3 Type summary  29.11.2011 
 
 
 
 
Typenbezeichnung 
PME71.401A2 
PME71.402A2 
PME71.901A2 
PME72.521A2 
PME72.541A2 
PME73.810A2 
PME73.820A2 
PME73.830A2 
PME73.831A2 
PME73.840A2 
Mains voltage AC 230 V 
●  ●  ●  ●  ●  ●  ●  ●  ●  ● 
For use with LME71.000A... 
●  ●  ● 
---  ---  ---  ---  ---  ---  --- 
For use with LME72.000A...  ---  ---  --- 
●  ● 
---  ---  ---  ---  --- 
For use with LME73.000A...  ---  ---  ---  ---  --- 
●  ●  ●  ●  ● 
Gas program forced draft burner 
●  ●  ●  ●  ●  ●  ●  ●  ●  ● 
Gas program atmospheric burner  ---  ---  ---  ---  ---  ---  ---  ---  ---  --- 
1-stage/2-stage or 1-stage modulating 
●  ●  ●  ●  ●  ●  ●  ●  ●  ● 
Pilot burner simultaneously/alternately  --- 
● 
---  --- 
● 
---  --- 
●  ●  ● 
Modulating via actuator (pneumatic or mechanic gas-air 
ratio control) 
---  ---  --- 
●  ●  ●  ●  ●  ●  ● 
Modulating via PWM fan (pneumatic or mechanic gas-
air ratio control) 
---  --- 
● 
---  ---  ---  ---  ---  ---  --- 
Fan speed control/control via analog signal/3-position 
step signal 
---  --- 
● 
---  ---  ---  ---  ---  ---  --- 
Actuator control via analog signal/3-position step signal 
for actuator with potentiometer 
---  ---  ---  ---  --- 
● 
--- 
●  ● 
--- 
3-position signal for actuator without potentiometer  ---  ---  --- 
●  ● 
--- 
● 
--- 
●  ● 
Control sequence programmable time 
●  ●  ● 
---  --- 
●  ●  ●  ●  ● 
POC 
●  ●  ●  ●  ●  ●  ●  ● 
--- 
● 
Valve proving   ---  --- 
● 
---  --- 
●  ●  ●  ●  ● 
Input valve proving ON/Off  ---  ---  --- ---  ---  ---  ---  --- 
● 
--- 
 
Example: