35/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  4 Technical data  29.11.2011 
 
 
Ionization probe 
 
LME7...
M
C
ION
X10-05/2
X10-05/1
 
Figure 4: Measuring circuit for ionization probe 
 
Legend 
 
C  Electrolytic condenser 100...470 µF; DC 10...25 V 
ION Ionization probe 
M 
Microammeter Ri max. 5,000  
 
 
Warning! 
Simultaneous operation of QRA... and ionization probe is not permitted!  
If not observed, there is a risk of impairment of safety functions. 
 
Measuring circuit for detector 
current measurement