54/245 
Building Technologies Division  Basic Documentation LME7...   CC1P7105de 
Infrastructure & Cities Sector  10 PME71.401...  29.11.2011 
 
Value range Parameter 
number 
Parameter  Edit 
Min.  Max. 
Resolution  Factory setting  Password level 
reading from level 
Password level 
writing from level 
700  Error history               
701 Current error: 
00: Error code 
01: Startup meter reading 
02: MMI phase 
03: Power value 
Read only   
2 
0 
--- 
0% 
 
255 
999999 
--- 
100% 
 
1 
1 
--- 
1 
--- Service --- 
702  Error history former 1:  
00: Error code 
01: Startup meter reading 
02: MMI phase 
03: Power value 
Read only   
2 
0 
--- 
0% 
 
255 
999999 
--- 
100% 
 
1 
1 
--- 
1 
--- Service
  --- 
•           
 
 
•           
 
 
•           
 
 
711  Error history former 10:  
00: Error code 
01: Startup meter reading 
02: MMI phase 
03: Power value 
Read only   
2 
0 
--- 
0% 
 
255 
999999 
--- 
100% 
 
1 
1 
--- 
1 
--- Service
  --- 
             
900  Process data               
936  Normalized speed  Read only  0%  100%  0.01%  ---  Service  --- 
951  Mains voltage  Read only  0 V  LME71.000A1: 175 V 
LME71.000A2: 350 V 
1 V  ---  Service  --- 
954  Flame intensity  Read only  0%  100%  1%  ---  Service  ---