61/245 
Building Technologies Division  Basic Documentation LME7...   CC1P7105en 
Infrastructure & Cities Sector  11 PME71.402...  29.11.2011 
 
Parameter  Parameter  Edit  Value range  Resolution  Factory setting  Password level  Password level 
number      Min.  Max.      reading from level  writing from level 
200  Burner control               
224  Specified time air pressure switch   Edit  0 s  13.818 s  0.294 s  13.818 s  SO 
OEM
 
225  Prepurge time -2,1 seconds  Edit  0 s  1237 s  4.851 s  29.106 s  SO 
OEM
 
226  Preignition time   Edit  1.029 s  37.485 s  0.147 s  3.087 s  SO 
OEM
 
230  Interval: End of safety time – fuel valve 1 ON  Edit  3.234 s  74.97 s  0.294 s  3.234 s  SO 
OEM
 
231  Interval: Fuel valve 1 ON – pilot valve OFF  Edit  0 s  74.97 s  0.294 s  2.646 s  SO 
OEM
 
234  Postpurge time   Edit  0 s  1237 s  4.851 s  19.404 s  SO 
OEM
 
240  Repetition in the event of loss of flame during 
operation 
0 = none 
1 = none 
2 = 1 x repetition 
Edit 0  2  1  0  SO 
OEM
 
247  Continuous pilot (during operation) 
0 = OFF 
1 = ON 
Edit 0  1  1  0  SO 
OEM
 
257  Postignition time -0.3 seconds  Edit  0 s  13.23 s  0.147 s  2.205 s  SO 
OEM