Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  12 PME71.901...  29.11.2011 
 
Parameter  Parameter  Edit  Value range  Resolution  Factory setting  Password level  Password level 
number      Min.  Max.      reading from level  writing from level 
700  Error history               
701.00  Current error: Error code  Read only  2  255  1  ---  Service  --- 
701.01  Current error: Startup meter reading 
Read only
 
0 999999 1 ---  Service --- 
701.02  Current error: MMI phase 
Read only
 
--- ---  --- ---  Service --- 
701.03  Current error: Power value 
Read only
 
0% 100% 1 ---  Service  --- 
702.00  Error history former 1: Error code 
Read only
 
2 255 1 ---  Service  --- 
702.01  Error history o1: Startup meter reading 
Read only
 
0 999999 1 ---  Service  --- 
702.02  Error history o1: MMI phase 
Read only
 
--- ---  --- ---  Service  --- 
702.03  Error history o1: Power value 
Read only
 
0% 100% 1 ---  Service  --- 
•          
 
 
•          
 
 
•          
 
 
711.00  Error history former 10: Error code 
Read only
 
2 255 1 ---  Service  --- 
711.01  Error history former 10: Startup meter reading 
Read only
 
0 999999 1 ---  Service  --- 
711.02  Error history former 10: MMI phase 
Read only
 
--- ---  --- ---  Service  --- 
711.03  Error history former 10: Power value 
Read only
 
0% 100% 1 ---  Service  --- 
 
 
        
900  Process data               
920  Current PWM signal fan  Read only  0%  100%  1%  ---  Service 
--- 
936  Normalized speed  Read only  0%  100%  0.01%  ---  Service  --- 
951  Mains voltage  Read only  0 V  LME71.000A1: 175 V 
LME71.000A2: 350 V 
1 V  --- 
Service
 
--- 
954  Flame intensity  Read only  0%  100%  1%  --- 
Service
 
---