TechnicalInstructions LMVSeries
DocumentNo.LV31000
Section2 Page2 SCCInc.
Grounds
TheLMV3hastwodifferenttypesofgrounds:
ProtectiveEarth(PE)
ReferenceGround(GND)
ProtectiveEarth
Protective Earth (PE) or chassis ground must always be connected to the control panel grounding lug.
ThepurposeofPEistoprovideagroundforall120VACconnecti ons.
Onewirefromthesecondaryside
of the control panel’s main stepdown transformer should also be connected to the control panel
groundinglug.
AllofthePEterminalsontheLMV3arecommon.
ReferenceGround
The other type of ground is the Reference Ground (GND). These are found on
the low voltage
connections.ThepurposeoftheReferenceGroundistoserveasadatumtomeasureothervoltages.