EasyManua.ls Logo

Siemens LMV3 series - Page 60

Siemens LMV3 series
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LMV Series
Technical Instructions
LV3-1000
Gas Oil Gas Oil U/S/O Default Range Description
Parameter #
Fuel 0
Fuel 1
LEGEND - Password Access: U = User, S = Service, O = OEM, U/S = View - User, Write - Service, S/O = View - Service, Write - OEM
Shaded Parameters = Frequently Used. ** Parameters = Must Set. Fuel 1 parameters for LMV36 only.
Parameter Name
VSD Speed Shift S/O 0 0-4
This setting enables 4-20 mA input X64 as the input for shifting the VSD speed off of the base curve. If
activated, terminal X64 will no longer accept a 4-20 mA input for the load. There are two additional options
to consider when activating VSD shift. The first is to enable the controller sending the 4-20 mA signal to
test the analog input during phases 24-30 (prepurge). The second is to enable ignition speed shift so that
the VSD speed at ignition position can be shifted to provide a more rich light off when the boiler is cold.
0 = deactivated (X64 remains as a 4-20 mA load input)
1 = activated
2 = activated (with analog input test)
3 = activated (with ignition speed shift)
4 = activated (with analog input test and ignition speed shift)
VSD Activation 0 0-1
This setting activates or deactivates a VSD:
0 = VSD deactivated
1 = VSD activated
Modulation Ramp 32 sec 32-80 sec
This setting controls the speed at which the actuators will ramp during phases 60-62 (fuel valves open). The
time chosen is how long it would actually take for the actuators to drive from 0-90°. During all other
phases, the actuator ramp speed is fixed depending on the model of the SQM33 actuator being used
(SQM33.5 = 5 sec, SQM33.7 = 17 sec). If using a VSD, this time should be set at least 20% longer than the
longest VSD ramp time (parameters 522 and 523).
Load Low Fire Not set 20-100% Sets the low fire load. During normal operation, the burner will not modulate below this point.
Load High Fire Not set 20-100% Sets the high fire load. During normal operation, the burner will not modulate above this point.
VSD Shift Low -4% -15-0%
Sets the absolute lower limit for VSD speed shift. This percentage is based on the standardized speed
(parameter 642).
VSD Shift High 4% 0-25%
Sets the absolute upper limit for VSD speed shift. This percentage is based on the standardized speed
(parameter 642).
Shift Attenuation 88% 0-100%
The attenuation factor for VSD speed shift. This setting gives the ability to have less VSD shift at low fire for
a given analog input signal. 100% attenuation means that there will be no shift at low fire and maximum
shift at high fire with a linear interpolation between. A setting of 0% results in no attenuation, so the full
measure of VSD shift will be used at all firing rates.
Shift Delay 25 sec 0-255 sec
This setting is a delay timer for VSD speed shift. After the LMV3 reaches normal operation (phase 60), this
delay timer starts. After this time expires, the 4-20 mA input on X64 will be used to shift the VSD speed. A
setting of 0 seconds deactivates this feature.
Shift Limit Time 0 sec 0-3600 sec
If the LMV3 is at the upper or lower VSD shift limit (parameters 547/567 or 548/568) for this amount of
time, a warning message will be displayed or a shutdown will occur, depending on the setting of parameter
552/572. A setting of 0 seconds deactivates this feature.
Shift Limit Response 0 0-2
Determines the action of the LMV3 if the VSD shift limits are reached:
0 = warning only
1 = warning and VSD shift deactivation
2 = shutdown
S/O
551
567
568
569
570
571
546 566
542
552 572
530
544
545 565
S
547
548
549
550
SCC Inc. Page 12 Section 3

Table of Contents

Other manuals for Siemens LMV3 series

Related product manuals