105/213 
Building Technologies  Basic documentation LMV37.4...  CC1P7546en 
HVAC Products  11 Fan control  01.12.2009 
 
Value Error  Recommended measures 
-6  Unplausible sensor signals 
The required pulse pattern (60°, 120°, 180°) has not 
been correctly identified. 
 
1. Speed sensor does not detect all tappets of the 
  sensor disk 
→ check the distance. 
2. As the motor turns, other metal parts are detected 
  also, in addition to the tappets 
→ improve mount-
ing. 
3. Electromagnetic interference on the sensor lines 
→ 
  check cable routing, improve EMC. 
-7  Invalid standardized speed 
Standardized speed measured does not lie in the 
permissible range. 
 
1. Motor turns too slowly or too fast. 
-15  Speed deviation µC1 + µC2 
The speeds of microcomputer 1 and 2 deviated too 
much. This can be caused by wrong standardized 
speeds (e.g. after restoring a data set to a new unit) 
→ repeat standardization and check the fuel-air ratio 
-20  Wrong phase of phase manager 
Standardization was made in a wrong phase. 
 
1. Permitted are only phases 
≤12 → controller OFF, 
   start standardization again. 
-21  Safety loop / burner flange open 
Safety loop or burner flange is open. 
 
1. Repeat standardization with safety loop closed. 
-22  Air actuator not referenced 
Air actuator is not referenced or has lost its reference 
 
1. Check if the reference position can be approached. 
2. Check if actuators have been mixed up. 
3. If error only occurs after standardization was star-
ted, the actuator is possibly overloaded and cannot 
reach the required position. 
-23 VSD deactivated 
Standardization was started with VSD deactivated → 
activate VSD and repeat standardization 
-24  No valid operating mode 
Standardization was started with no valid operating 
mode  
→ select a valid operating mode and repeat standardi-
zation 
 
The result of speed standardization (100% speed) can be read out via parameter. The 
speeds acquired by the 2 microcontrollers can differ by about 1.5%, the reason being 
slightly different resonator frequencies. 
 
Parameter 
642.0  Standardized speed of μC1 
642.1  Standardized speed of μC2 
 
11.12  Control of fan motor with pneumatic air-
fuel ratio control
  
 
If the control of the fan motor is employed for burners with pneumatic air-fuel ratio con-
trol, only the control path is used. There is no need to connect a speed feedback signal 
and to have speed control (for operating modes, refer to chapter 
Selection of operating 
mode
).