LMVSeries TechnicalInstructions
 LV51000
SCCInc. Page47 Section3
33:SequenceDiagrams
The Siemens LMV5 BMS can perform a number of different burner sequences based upon how certain parameters are set.
Althoughthereareanumberofparametersthataffectsmallaspectsoftheburnersequence,themainparametersthataffectthe
sequenceareparametersFuelTrainGasandFuelTrainOil.
TheseparameterssettheframeworkofthesequenceandarebaseduponthefueltraindiagramsinSection4.TheOEMhasthe
optionofselectingoneofthreedifferentgastrainswiththeirassociatedsequencediagrams,andoneoffourdifferentoiltrains
withtheirassociated sequencediagrams(the sequencediagramsand fueltraindiagramsfordirectsparkignition withheavyoil
havebeenomitted).
ThesequencediagramsinSection33illustratewheninputandoutputterminalsareexpectedtobe energizedordeenergized.A
legendonthebottomofeachpagedescribesthevarioussymbolsusedinthediagrams.Thelastdiagramdescribeswhatpositions
the attached actuators are expected to achieve at each phase and outlines the method that is used to check the actuators
position.
Notes:
1) Onlyonefuelselectterminalcanbeenergizedatatime.Ifbothterminalsareenergized,theLMV5willgointolockout.If
neitherterminalisenergized,fuelselectionisinternalthroughtheAZL5(FuelSelect)orviaModbus.
2) Theexternalburneron/offswitchcanbedisabledwithparameterInputController.Ifactivated,thisterminalneedstobe
energized to have the LMV5 start its sequence.The function of terminal X503.1 becomes “burner on / off” when any
externalloadcontrolmodeisselected.
3) ThealarmcanbesilencedthroughtheAZL(Alarmact/deact).ThisalarmsilenceresetswhentheLMV5isresetorrestarted.
4) Whenusingan LMV52, continuouspilotispossible (ContPilotGas /ContPilotOil).Ifcontinuouspilot isactivated,the pilot
valvewillremainenergizedthroughphase62.
5) IfparameterGasPressureMinissettoactivated,thelowgaspressureswitchisexpectedtoremainclosedduringphases21
50ofLOwGaspandHOwGasp,ensuringadequategaspressureforthepilot.IfGasPressureMinissettoDeactxOGP,the
lowgaspressureswitchisexpectedtoremainclosedonlywhenfiringgasandisnotcheckedwhenfiringoil.