LMVSeriesTechnicalInstructions 
DocumentNo.LV5‐1000
SCCInc. Page9 Section6
SuggestedO
2
TrimCommissioning‐TraditionalNozzleMixingBurnerwithNoorLow
PercentageFGR(TypicallyLMV52.240)
1.  Thecommissi oningprocedureassumesthefollowing:
a.  AllPre‐RequisitesforanLMV52systemwithO
2
trim(andVSDifequipped)havebeenmet
accordingtoSection4ofthisliterature.
b.  TheRatioControlCurveshavebeencommissionedaccordingtoSection4ofthisliterature.
c.  Section6ofthisliteraturehasbeenreadand un derstooduptothispoint.
2.  AswasthecasefortheRatioControlCurvesinSection4,thesamefreespreadsheetcanalsobe
usedtoassistinthecommissioningoftheO
2
trim.ThisspreadsheetgraphicallyillustratestheO
2
curvesaswellasprovidesanorderlywaytorecordthedetailsofhowtheburnerwassetup.
Figure6‐3:LMVxCurvesSpreadsheet
3.  ThekeytocommissioningtheO
2
curvesquicklyandeasilyiscontainedintheRatioControlCurves.
Specifically,thefollowingmustbeachievedforeachpointontheRatioControl Curves(as
paraphrasedfromSection4ofthisliterature):
a.  Safe,efficientcombustionasverifiedbyacalibratedstackgasanalyzer
b.  The%loadmatchingthefuelflowwithin+/‐3%
c.  Emissionscompliance
d.  SmoothRatioControlCurves(nosharppeaksorvalleys)
e.  VSDspeedshouldincreasewithloadinalinearfashion(ifequipped)
f.  Findandreco
rdthe%O
2
wetcorrespondingtothefuelrichlimit(O2Alarmvalue)foreachpoint
byprobing.*
g.  Findandrecordthe%O
2
wetcorrespondingtothefuelleanlimit(O2MaxValue)forPoint1and
Point10byprobing.*
h.  Lastbutnotleast,leavethecurvepointssothatthe%O
2
wetis2%higherthanthefuelrichlimit
(O2Alarmvalue).Recordthisasthe"saved"valueforeachcurvepoint.
*NOTE:Whenprobingthefuelrichlimit,itisnotrecommendedtoexceed200PPMCO(drybasis)
orlessthan1.0%O
2
(wetordrybasis)foranypoint.Whenprobingthefuelleanlimit,itisnot
recommendedtoexceed200PPMCOoradverselyaffectflamestabilityforanypoint.