TechnicalInstructions  LMVSeries
DocumentNo.LV51000
Section6 Page4 SCCInc.
Formanynozzlemixingburners(traditionalboilerburners),theO
2
setpointwillbeahighervalueatlow
fireandalowervalueathighfire.Thisistruesincemostnozzlemixingburnersneedmoreexcessair
(higherO
2
)atlowfiretoachievecompletecombustion.ForthistypeofburneranO
2
setpointof5%O
2
(wet)atlowfireandanO
2
setpointof2%O
2
(wet)athighfireisnotuncommon.
Precontrol
Asmentionedabove,allO
2
trimsystemswithanO
2
sensorintheboiler'sexhaustmustuse"old"O
2
readingsduetophysicalrealitiesoftheboiler.Thisfact,combinedwithanO
2
setpointthattypically
variesfromlowfiretohighfiremeansthattheO
2
trimsystemcannotactivelytrimwhentheburner
makesalargechangeinfiringrate.ThisbegsthequestionofwhathappenstotheO
2
trimwhenthe
burnertransitionsfrom20%firingrateto,say,80%firingrate.TheansweristheO
2
trimchangesmodes
fromactivetrimtowhatisreferredtoas"precontrol".
PrecontrolispossiblebecausetheLMV52learnsthecharacteristicoftheburnerateachpointonthe
curveduringtheO
2
trimcommissioning.ThespecificcharacteristicthattheLMV52learnsishowmuch
ofachangeinairflow(airrate)isnecessarytoachieveacertainchangeinthe%O
2
.Thisspecific
characteristicisknownastheLambdaFactor,andisessentiallytheburner'ssignaturefromanO
2
trim
standpoint.Justlikethedelaytime(Tautime)thatwasmentionedearlier,itisnecessaryforthefuel
flowtomatchtheloadnumbersothattheLambdaFactoriscorrectandaccurateforeachpoint.
PrecontrolusestheLambdaFactorsothattheburnercanbemodulatedwhilekeepingthe%O
2
closeto
theO
2
setpoint,eventhoughthesetpointchangeswiththefiringrateandtheO
2
trimisusing"old"O
2
readings.Oncetheburnerstopsmodulatingoronlymodulatesasmallamount(+/‐5%),theO
2
trimwill
changemodesbackto"active"andperformactiveO
2
trimonceagain.
AproperlycommissionedO
2
trimsystemwilltypicallymaintainthe%O
2
setpointwithadeviationof+/‐
0.1%O
2
whentheburnerisnotmodulatingasignificantamount(+/‐5%loadchange).Withthissmall
loadchange,theO
2
trimwillstayinthe"active"mode.Whensignificantmodulationisencountered(+/‐
15%loadchange),theprecontrolwillengageandthedeviationfromsetpointwillincrease.Deviations
of+/‐0.3%orlessaretypicalduringmodulationwhentheprecontrolisengaged.
O
2
TrimTerminology
1. %O
2
WetInsituO
2
sensors,liketheQGO20sensorthatisusedwiththeLMV52,readthe%O
2
ona
wetbasis.Thisisincontrasttothevastmajorityofportablecombustionanalyzersthatread%O
2
on
adrybasis.%O
2
wetshouldalwaysbealowervaluethan%O
2
dry.Figure611(locatedlaterin this
section)givestheapproximaterelationshipbe tween%O
2
wetand%O
2
dry.
2. TauTime‐Thisisthedelaytimebetweenwhenanadjustmentismadeattheburner(movingthe
airdamper,etc.)andwhenthatadjustmentisreadattheO
2
sensor.Foragivenburner/boiler,this
timewillbeshorterathighfireandlongeratlowfire.
3. O
2
RatioControl‐Thisisthemeasured%O
2
wetwhentheactuators/VSDareontheFuelAirRatio
ControlCurveandarenotbeingtrimmed.ThisisrecordedforeachpointonthecurveexceptPoint
1.Thisisalsocommonlyreferredtoasthe“leancurve”.