LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page31 Section4
SensOperPhGas Enables twoflamedetectorstobeusedononeburner(LMV52only).
ValveProvingType Enables gas valve proving onstartuporshutdownorboth.This type of testing
ensures that the gas valves are closed, and that the valve seats are in good
condition.
StartPointOp Can adjust which curve point the LMV5 will drive to after light off.This setting
doesnotaffectturndown.
NumFuelActuato
rs PermitstheLMV5torundualfuelwithasingleactuator‐twofuelvalvesonone
actuator.
ProgramStop StopstheLMV5ataparticularphaseinthestartuporshutdownsequence.This
isparticularlyusefulwhensettoPhase44fortuni
ngthepilot.
FGRMode On an LMV52, this setting enables only the Aux 3 actuator to be held from
modulatin
g until a certain temperature or time after light off is met.This is
usually used to delay the use of FGR until a certain time or until a stack
temperatureismet.
ReleasecontctVSD IfaVSD isbeingused, this enablestheblower to coastdownafter
postpurgeis
complete.
O2SensServTim This setsaserviceintervalfortheO
2
sensor.
HOME