Page 32 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB05
mmmmm
Operation
Security
The Lock parameter P000 secures the MultiRanger against parameter changes. The unit
can still be put into PROGRAM mode when locked, and parameter values can be viewed,
but no parameter values can be changed.
When P000 is set to 1954, programming is enabled. To disable programming, enter
another value.
P000 (1954) is a fixed value password. Therefore, you should use other means to secure
the MultiRanger if security is a concern.
Simulation
P000 Lock also controls how simulations affect control relays. By default, control relays
are unaffected by simulation levels. But if P000 is set to 1, they react to the simulated
level. See
Parameters P925–P927
on page 220 for running a simulation.
Using Units or Percent (%)
Many parameters can be viewed either in measurement units (P005) or as a percentage.
View the parameter and then press MODE to toggle between units and percentage.
The LCD shows the selected measurement type, either units (m, ft) or percentage (%).
MR 200 only:
Percentage is also available when showing flow and volume with 100%, based on the
parameter that defines the maximum.
Parameters Types
View Only Parameters
Parameter values indicating status only. They cannot be altered.
Global Values
Parameter values common to all inputs and outputs on the MultiRanger.
When a global parameter is accessed, the index display automatically disappears. When
a non-global parameter is accessed, the index display reappears showing the last index
number.
Measurement Maximum
Volume P051
Flow P604