Page 38 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB05
mmmmm
Operation
3
Average or Differential [MR 200 only]
For differential or average operation with a single-point MultiRanger, set P001 to 4
(differential) or 5 (average) and connect two
transducers of the same type. All of the relevant
parameters then become indexed by the correct
transducer:
Dual Point Models
The MultiRanger starts in an OFF state and does not take level measurements. For
measurement setup, configure these basic parameters:
If the application uses two measurement points, provide the basic information for each
measurement point separately:
Index Description
2 indexed by Transducer One or Two
3 indexed by level measurement
1 = Transducer One
2 = Transducer Two
3 = Calculated Level (average or difference)
Parameter Index Value Description
P001
1 1 Operation = level
2 3 Operation = distance
P002
1 1
Material = Liquid
2 1
P003
1 2 Max. Process Speed = medium
2 3 Max. Process Speed = fast
P004
1 104 Transducer = XPS - 15
2 102 Transducer = XPS - 10
P005 G 1 Units = meters
P006
1 12 Empty = 12m
2 4 Empty = 4m
P007
111Span = 11m
2 3.5 Span = 3.5m
Relay Number
Ring indicates
relay is configured
Dot indicates relay
is energized/de-
energized