Loading...
7ML19981FB05 MultiRanger 100/200 – INSTRUCTION MANUAL Page 229
mmmmm
Appendix B: Tech Reference
Universal, Linear [MR 200]
Please note that the Universal, Linear feature is only available on the MultiRanger 200.
Set P600 = 4.
This flow calculation creates a piece-wise linear approximation of the head/flow curve.
This option provides best results if the curve has sharp angles joining relatively linear
sections.
Enter a Head Breakpoint at each point where the head/flow curve bends sharply (2
minimum). For combination curves (mostly linear but include 1 or more arcs), enter
numerous breakpoints along the arc, for best flow calculation accuracy.
See also
Typical Flow Characterization
on page 82.
Universal, Curved [MR 200]
Please note that the Universal, Curved feature is only available on the MultiRanger 200.
This calculation creates a cubic spline approximation of the head/flow curve, providing
best results if the curve is non-linear, and there are no sharp angles.
Select at least enough breakpoints from the curve to satisfy the following:
two breakpoints very near the minimum head
one breakpoint at the tangent points of each arc
one breakpoint at each arc apex
two breakpoints very near the maximum head