&20081,&$7,216 ,QWHUQDWLRQDO(QJOLVK
MICROMASTER 420 Reference Manual
46 Issue A1
WK
:RUG
WK
:RUG%LW 3:( 
QG
SDUDPHWHUYDOXH
Bits15 - 0 = 2
nd
Parameter value for array parameters and task
for all elements.
When value of P2013
= 4 (fixed) or
= 127 (variable length)
and single word parameter.
= Low word of parameter value (no array).
= Low word of n
th
parameter value for array
parameter and task for n
th
element.
When value of P2013
= 4 (fixed) or
= 127 (variable length)
and double word parameter.
= Low word of 1
st
parameter value for array parameter
and task for all elements.
When value of P2013.
= 127 (variable length)
and 32 bits parameter.
= Next accessible ID. Slave
Å
Master and replay ID =
Task cannot be executed.
Error value = ID not exist or ID
not accessible.
When value of P2013
= 127 (variable length).
= Next or previous valid value (16 bit).
= High word of the next or previous valid value (32
bit).
In the right order:
If new value > actual value
Å
next valid value.
If new value < actual value
Å
previous valid value.
Slave
Å
Master and replay ID =
Task cannot be executed.
Error value = Value no
admissible or New max. /min.
value exist.
When value of P2013
= 127 (variable length).
1RWHV
If a parameter value is requested by the master, the values in PWE1 and
PWE2 of the master telegram to the inverter are ignored.
The meaning of the 3
rd
and 4
th
words, PWE1 and PWE2 is dependent on
whether variable or fixed length PKW has been selected using P2013.
The examples should explain this more clearly later in this section.
The MICROMASTER 420 parameter list must be consulted to understand
the meaning of the parameter values, and their appropriate settings.