Page 10 MFA 4p – INSTRUCTION MANUAL 7ML19985FM01
mmmmm
Wiring
Connection to power:
Terminal 10 must be connected to reliable ground.
The equipment must be protected by a 15A fuse or circuit breaker in the building
installation.
A circuit breaker or switch in the building installation, marked as the disconnect
switch, shall be in close proximity to the equipment and within easy reach of the
operator.
AC input circuit, relay circuits, min. 14 AWG copper wire
Recommended torque on terminal clamping screws, 7 in.lbs. max.
WARNING: All field wiring must have insulation suitable for at least
250 V.
NO NONC
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
PROBE
INPUT
9
9
10
10
11
11
12
12
L2/N
RL1 RL2
L1
RELAYS SHOWN IN
DE-ENERGIZED POSITION
250 V 8 AMP
NC
7ML19985FM01.book Page 10 Wednesday, May 21, 2008 2:17 PM