Page 10 MFA 4p – INSTRUCTION MANUAL 7ML19985FM01
mmmmm
Wiring
Connection to power:
• Terminal 10 must be connected to reliable ground.
• The equipment must be protected by a 15A fuse or circuit breaker in the building
installation.
• A circuit breaker or switch in the building installation, marked as the disconnect
switch, shall be in close proximity to the equipment and within easy reach of the
operator.
• AC input circuit, relay circuits, min. 14 AWG copper wire
• Recommended torque on terminal clamping screws, 7 in.lbs. max.
WARNING: All field wiring must have insulation suitable for at least
250 V.