Appendix
A.3 Application examples for functional safety (STO / SS1-t)
Power Module PM330
Hardware Installation Manual, 12/2018, A5E32844552B AF
131
Scenario 2:
LED 1 DEVICE is OFF
-> fault
LED 2 OUT is OFF
-> the safety circuit is not enabled
Possible causes:
3SK1 power supply missing
Short or cross-circuit faults at the 3SK1
Between the cycle outputs
In or to the power supply
In the input circuit (sensor circuit)
In the enable circuits
In the feedback signal circuit
Safety relay 3SK1 Advanced or 3SK1112… being used
Scenario 3:
LED 1 DEVICE lights up green
-> power supply, power up and configuration are OK
LED 2 OUT is OFF
-> the safety circuit is not enabled
Possible causes:
LED 3 IN is OFF
-> close sensor circuit through 2 channels
LED 3 IN flashes green
LED 4 SF is OFF -> START button not pressed
LED 4 SF flashes red-> simultaneity for 1x2 channel sensor not met
LED 4 SF flashes red-> time monitoring for two-handed start violated
LED 3 IN flashes yellow
LED 4 SF flashes red -> short-circuit T1/T2 with respect to ground or 24 V