Technical specifications
6.1 General technical data
Power Module PM330
82 Hardware Installation Manual, 12/2018, A5E32844552B AF
Table 6- 1 General technical data
Line system configurations Grounded TN/TT systems or ungrounded IT systems (a grounded phase conductor is not
permissible in 690 V line supplies)
Line requirement A line reactor (2% u
k
) must be connected in series
Line voltage 380 V (-10 %) ... 480 V (+10 %)
500 V (-10 %) ... 690 V (+10 %)
Output frequency 0 ... 150 Hz
(selecting an output frequency greater than 100 Hz works from SINAMICS firmware V4.7
Displacement factor cos φ
0.96
0.75 ... 0.93 (with line reactor u
k
= 2%)
Short-circuit current rating
according to IEC, in conjunc-
tion with the specified fuses
160 ... 630 kW: 100 kA
Short-circuit current rating
according to UL61800-5-1
(up to 480 V AC or 600 V
AC), in conjunction with the
specified fuses
160 ... 630 kW: 100 kA
Can be used on line supplies that cannot supply more than 100 kA symmetrically at a max-
imum voltage of 480 V AC or 600 V AC when they are protected with the semiconductor
fuses specified in Chapter "Technical Data" of this manual.
III according to EN 61800-5-1
Electromagnetic compatibility
(EMC)
Emitted interference
• Standard
• with line filter
• Category C3 (second environment) according to EN 61800-3
1)
• Category C2 (first
*)
and second environments) according to EN 61800-3
*)
When used in the first environment, an appropriately trained and authorized technical
person must set up the drive and commission it.
NOTE: An appropriately trained and authorized technician is person or organization with
the required experience for setting up and/or for commissioning the drive systems, including
the associated EMC aspects.
Use in the first and second environment according to EN 61800-3
according to EN 61800-5-1: Class I (with protective conductor system) and Class III (PELV)
Forced air cooling AF according to EN 60146
Sound pressure level
PA
≤ 74 dB(A)
2)
according to EN 61800-5-1: For the intended purpose