Appendix
A.4 Acceptance test/configuration test
Power Module PM330
138 Hardware Installation Manual, 12/2018, A5E32844552B AF
Status
3.
Activate SS1-t
3.1. Activate SS1-t while the motor is running.
3.2.
Check the following:
The motor brakes along the OFF3 ramp.
OFF3 ramp is active (r0899.5 = 1)
After the "SS1-t delay time" expires, the inverter signals:
r0002 = [44] Switching on inhibited connect 24 V to terminal STO (hardware)
The inverter signals neither faults nor alarms.
3.3. Check the status LEDs of the safety relay
(here in the example, a 3SK112x-…)
LED (1) DEVICE = green
LED (2) OUT = green/yellow flashing
-> instantaneous (non-delayed) output circuit of the 3SK1 open. (OFF2 control)
-> delayed output circuit of the 3SK1 still closed. (STO circuit)
After the time set at the 3SK1 rotary controller has expired
LED (2) OUT = off -> both 3SK1 output circuits open
LED (3) IN = off -> 3SK1 switch-on (close) conditions not satisfied
Here, input circuit closed
LED (4) SF = OFF
4.
Deactivate SS1-t
4.1.
Deactivate SS1.
4.2.
Check the following:
STO is not active (r0002 ≠ 44).
(e.g. R0002 = [31] Ready for switching on set "ON/OFF1" = "1/0" (p0840)
The inverter signals neither faults nor alarms.
4.3. Check the status LEDs of the safety relay
(here in the example, a 3SK112x-…)
LED (1) DEVICE = green
LED (2) OUT = green-> 3SK1 output circuit closed
LED (3) IN = green-> 3SK1 switch-on (close) conditions satisfied
Input circuit closed
Feedback circuit closed
Start button where necessary actuated
LED (4) SF = OFF