Technical specifications
6.2 Specific technical data
Power Module PM330
94 Hardware Installation Manual, 12/2018, A5E32844552B AF
Table 6- 5 PM330, frame size HX, 3-phase 500 690 VAC, Part 1
Article No.
6SL3310-
1PG33-7AA0
1PG34-0AA0
1PG34-5AA0
Rated input current
- at 500 V, 45 °C
- at 600 V, 45 °C
- at 690 V, 45 °C
- at 500 V, 55 °C
- at 600 V, 55 °C
- at 690 V, 55 °C
383 A
367 A
354 A
326 A
312 A
301 A
416 A
412 A
409 A
354 A
350 A
348 A
471 A
459 A
447 A
400 A
390 A
380 A
Rated input current DCP/DCN
(for 2/3 of the inverter power)
- at 675 V
DC
, 45 °C
- at 810 V
DC
, 45 °C
- at 930 V
DC
, 45 °C
- at 675 V
DC
, 55 °C
- at 810 V
DC
, 55 °C
- at 930 V
DC
, 55 °C
314 A
301 A
290 A
267 A
255 A
246 A
341 A
337 A
335 A
290 A
287 A
284 A
385 A
376 A
366 A
328 A
319 A
311 A
Rated output current I
N
- at 500 V, 45 °C
- at 600 V, 45 °C
- at 690 V, 45 °C
- at 500 V, 55 °C
- at 600 V, 55 °C
- at 690 V, 55 °C
368 A
353 A
340 A
313 A
300 A
289 A
400 A
396 A
393 A
340 A
337 A
334 A
453 A
441 A
430 A
385 A
375 A
366 A
LO base load power
LO base load input current at 690 V
LO base load output current at 690 V
315 kW
343 A
330 A
355 kW
401 A
385 A
400 kW
437 A
420 A
HO base load power
HO base load input current at 690 V
HO base load output current at 690 V
250 kW
283 A
272 A
315 kW
327 A
314 A
355 kW
362 A
348 A
Fuse according to IEC
manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1333-2
(450 A/690 V)
Siemens AG
≤ 100 kA
> 3.5 kA
3NE1334-2
(500 A/690 V)
Siemens AG
≤ 100 kA
> 4.5 kA
3NE1435-2
(560 A/690 V)
Siemens AG
≤ 100 kA
> 7.0 kA
Fuse in compliance with UL
2)
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1333-2
(450 A/690 V)
Siemens AG
≤ 100 kA
> 3.5 kA
3NE1334-2
(500 A/690 V)
Siemens AG
≤ 100 kA
> 4.5 kA
3NE1435-2
(560 A/690 V)
Siemens AG
≤ 100 kA
> 7.0 kA
max. power loss, at I
N
, 45 °C, 690 V
5.402 kW
6.191 kW
6.884 kW
Required cooling air flow
360 l/s
360 l/s
360 l/s
Maximum connectable cross-section of the line,
motor and DC-link cable
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
Recommended cable cross-section for 500 V
- line cable
- motor cable
2 x 120 mm
2
2 x 120 mm²
2 x 150 mm
2
2 x 120 mm²
2 x 185 mm
2
2 x 150 mm²
Recommended cable cross-section for 690 V
- line cable
- motor cable
2 x 120 mm
2
2 x 95 mm²
2 x 150 mm
2
2 x 120 mm²
2 x 185 mm
2
2 x 150 mm²