Certification
6.2EMC and Environmental Type Tests
Test Description Test Levels Severity Levels
IEC 61000-4-10 Damped
Oscillating
Magnetic Field
Enclosure Ports 100 A/m for
1 s (100 kHz
and 1 MHz)
5
IEC 61000-4-11 Voltage Dips
and Interrupts
AC Power Ports 30% for 1 period
60% for 50 periods
100% for 5 periods
100% for
50 periods
Signal Ports
DC Power Ports
IEC 61000-4-12 Damped
Oscillatory
AC Power Ports
2.5 kV Common
1 kV Differential
Mode @ 1 MHz
3
Signal Ports
DC Power Ports
IEC 61000-4-16 Mains Frequency
Voltage
AC Power Ports
30 V for 60 s
300 V for 1 s
4
IEC 61000-4-17 Ripple on DC
Power Supply
DC Power Ports 10% 3
Signal Ports 2.5 kV
Common Mode
1.0 kV
Differential Mode
DC Power Ports
IEC 61000-4-18 Damped
Oscillatory Wave
AC Power Ports
2.5 kV
Common Mode
3
IEC 61000-4-29 Voltage Dips
and Interrupts
DC Power Ports 30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal Ports 2 kVAC (Fail-Safe
Relay Output)
DC Power Ports 1.5 kVDC
Dielectric Strength
AC Power Ports 2 kV
Signal Ports 5 kV (Fail-Safe
Relay Output)
DC Power Ports
IEC 60255-5
HV Impulse
AC Power Ports
5 kV
a
Siemens-specified severity levels
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RSG2488 meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
RUGGEDCOM RSG2488
Installation Manual, 07/2021, C79000-G8976-1048-11
41