Operating
line
Operating
level
Function
Default value
Min
Max
Unit
947 F Flow temp setp incr hygro 10 / 1 20 °C
948 I Flow setp incr start at r.h. 60 0 100 %
950 I Flow temp diff dewpoint 2 / 0 5 °C
962 F With buffer
No ¦ Yes
No -
963 F With prim contr/system pump
No ¦ Yes
No -
969 F Optg mode changeover
None ¦ Off ¦ Automatic
Off. -
Heating circuit 2
1010 E Comfort cooling setpoint 20.0 Operating line
1012
Operating line 1016 °C
1012 E Reduced setpoint 19 Operating line
1014
Operating line 1010 °C
1014 E Frost protection setpoint 10.0 4 Operating line 1012 °C
1016 F Comfort setpoint max 35.0 Operating line
1010
35 °C
1020 E Heating curve slope 0.8 0.10 4.00 -
1021 F Heating curve displacement 0.0 -4.5 4.5 °C
1026 F Heating curve adaption
Off ¦ On
Off. -
1030 E Summer/winter heating limit 18 / 8 30 °C
1032 F 24-hour heating limit -3 / -10 10 °C
1040 I Flow temp setpoint min 8 8 Operating line 1041 °C
1041 I Flow temp setpoint max 80 Operating line
1040
95 °C
1050 F Room influence 20 / 1 100 %
1060 F Room temperature limitation 1 / 0.5 4 °C
1070 F Boost heating 5 / 0 20 °C
1080 F Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot setpoint
Down to reduced setpoint -
1090 F Optimum start control max 0:00:00 00:00:00 00:06:00 h /min / s
1091 F Optimum top control max 0:00:00 00:00:00 00:06:00 h /min / s
1100 F Reduced setpoint increase start / -30 10 °C
1101 F Reduced setpoint increase end -15 -30 Operating line 1100 °C
1120 F Overtemp prot pump circuit
Off ¦ On
On. -
1130 F Mixing valve boost 0 0 50 °C
1132 F Actuator:type
2-position ¦ 3-position
3-position -
1133 F Switching differential
2-pos
2 0 20 °C
1134 F Actuator running time 120 30 873 s
1150 I Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦ Functional/curing
heating¦ Curing/functional heating ¦ Manually
Off. -
1151 E Floor curing setpoint manually 25 0 95 °C
1156 E Floor curing day current 0 32 °C
1157 I Floor curing days complete 0 0 32 -
1161 F Excess heat draw
Off ¦ Heating mode ¦ Always
Always
1170 F With buffer Yes -
50/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 5 Handling 28. September 2009