Operating
line
Operating
level
Function
Default value
Min
Max
Unit
No ¦ Yes
1172 F With primary controller / system pump
No ¦ Yes
Yes
1200 I Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Protection
Heating circuit P
1300 E Operating mode
Protection ¦ Automatic ¦ Reduced ¦ Comfort
Automatically -
1310 E Comfort cooling setpoint 20.0 Operating line
1312
Operating line 1316 °C
1312 E Reduced setpoint 19 Operating line
1314
Operating line 1310 °C
1314 E Frost protection setpoint 10.0 4 Operating line 1312 °C
1316 F Comfort setpoint max 35.0 Operating line
1310
35 °C
1320 E Heating curve slope 0.8 0.10 4.00 -
1321 F Heating curve displacement 0.0 -4.5 4.5 °C
1326 F Heating curve adaption
Off ¦ On
Off. -
1330 E Summer/winter heating limit 18 − − − / 8 30 °C
1332 F 24-hour heating limit -3 − − − / -10 10 °C
1340 I Flow temp setpoint min 8 8 Operating line 1341 °C
1341 I Flow temp setpoint max 50 Operating line
1340
95 °C
1350 F Room influence 20 − − − / 1 100 %
1360 F Room temperature limitation 1 − − − / 0.5 4 °C
1370 F Boost heating − − − − − − / 0 20 °C
1380 F Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint -
1390 F Optimum start control max 0:00:00 00:00:00 00:06:00 h /min / s
1391 F Optimum top control max 0:00:00 00:00:00 00:06:00 h /min / s
1400 F Reduced setpoint increase start − − − − − − / -30 10 °C
1401 F Reduced setpoint increase end -15 -30 Operating line 1400 °C
1420 F Overtemp prot pump circuit
Off ¦ On
Off. -
1450 F Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually
Off. -
1451 F Floor curing setpoint manually 25 0 95 °C
1455 E Floor curing setpoint current 0 0 95 °C
1456 E Floor curing day current 0 0 32 -
1457 I Floor curing days complete 0 0 32 -
1461 F Excess heat draw
Off ¦ Heating mode ¦ Always
Always -
1470 F With buffer
No ¦ Yes
Yes -
1472 F With primary controller / system pump
No ¦ Yes
Yes -
1500 I Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Protection -
Domestic hot water
1610 E Nominal setpoint 50 Operating line TempBwMax °C
51/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 5 Handling 28. September 2009