Operating
line
Operating
level
Function
Default value
Min
Max
Unit
3176 E Yearly perf factor 9 --- 0 10
3176 E Fixed day 9 1.9.2004 31.12.2099 dd.MM.y
yyy
3177 E Heat delivered heating 9 0 0 9999999 kWh
3178 E Heat delivered DHW 9 0 0 9999999 kWh
3180 E Energy brought in heating 9 0 0 3500000 kWh
3181 E Energy brought in DHW 9 0 0 3500000 kWh
3183 E Yearly perf factor 10 --- 0 10
3183 E Fixed day 10 1.9.2004 31.12.2099 dd.MM.y
yyy
3184 E Heat delivered heating 10 0 0 9999999 kWh
3185 E Heat delivered DHW 10 0 0 9999999 kWh
3187 E Energy brought in heating 10 0 0 3500000 kWh
3188 E Energy brought in DHW 10 0 0 3500000 kWh
3190 F Reset fixed day storage
No ¦ Yes
No -
Cascade
3533 F Switch-on delay 5 0 120 min
3540 F Auto source seq ch’over 500 − − − / 10 990 h
3541 F Auto source seq exclusion
None ¦ First ¦ Last ¦ First and last
None
Supplementary source
3700 F Release below outside temp --- -50 50 °C
3701 F Release above outside temp --- -50 50 °C
3705 F Overrun time 10 0 120 min
3720 F Switching integral 50 0 500 °C*min
3722 F Switching differential Off 15 0 20 °C
3723 F Lock time 30 − − − / 0 120 min
Solar
3810 F Temp diff on 8 Operating line
3811
40 °C
3811 F Temp diff off 4 0 Operating line 3812 °C
3812 F Charg temp min DHW st tank − − − − − − / 8 95 °C
3815 F Charging temp min buffer − − − − − − / 8 95 °C
3818 F Charging temp min swi pool − − − − − − / 8 95 °C
3822 F Charging prio storage tank
None ¦ DHW storage tank ¦ Buffer
DHW storage tank -
3825 F Charging time relative prio − − − − − − / 2 60 min
3826 F Waiting time relative prio 5 1 40 min
3827 F Waiting time parallel op − − − − − − / 0 40 min
3828 F Delay secondary pump 60 0 600 s
3831 F Min run time collector pump 20 5 120 s
3834 F Collector start funct grad − − − − − − / 1 20 Min/°C
3840 F Collector frost protection − − − − − − / -20 5 °C
3850 F Collector overtemp prot − − − − − − / 30 350 °C
3860 F Evaporation heat carrier − − − − − − / 60 350 °C
3870 F Pump speed min 40 0 100 %
3871 F Pump speed max 100 0 100 %
3880 F Antifreeze None -