Operating
line
Operating
level
Function
Default value
Min
Max
Unit
None ¦ Ethylene glycol ¦ Propylene glycol ¦ Ethyl and propyl
glycol
3881 F Antifreeze concentration 30 1 100 %
3884 F Pump capacity 200 10 1500 l/h
Buffer storage tank
4708 F Forced charging setp cooling
− − −
6 35 °C
4709 I Forced charg setp heat min 40 20 80 °C
4710 I Forced charg setp heat max 50 20 80 °C
4711 I Forced charging time − − − − − − / 00:00 23:50 hh:mm
4712 I Forced charg duration max 4 1 20 h
4720 F Auto generation lock
None ¦ With B4 ¦ With B4 and B42/B41
With B4 -
4722 F Temp diff buffer/HC 0 -20 20 °C
4739 F Stratification protection
Off ¦ Always
Off. -
4750 F Charging temp max 80 8 95 °C
4755 F Recooling temp 60 8 95 °C
4756 F Recooling DHW/HCs
Off ¦ On
Off. -
4757 F Recooling collector
Off ¦ Summer ¦ Always
Off. -
4760 F Charg sensor el imm heater
With B4 ¦ With B42/B41
With B4 -
4761 F Forced charging electric
No ¦ Yes
No -
4783 F With solar integration
No ¦ Yes
No -
DHW storage tank
5020 F Flow setpoint boost 0 0 30 °C
5021 F Increase of transfer boost 8 0 30 °C
5022 F Type of charging
With B3 ¦ With B3/B31 ¦ With B3, legio B3/B31
With B3/B31
5024 F Switching differential 5 0 20 °C
5030 F Charging time limitation 240 − − − / 10 600 min
5050 F Charging temp max 80 8 BZ 5051 OEM °C
5055 F Recooling temp 80 8 95 °C
5056 F Recooling heat gen/HC
Off ¦ On
Off. -
5057 F Recooling collector
Off ¦ Summer ¦ Always
Off. -
5060 F El imm heater optg mode
Substitute ¦ Summer ¦ Always
Substitute -
5061 F Electric immersion heater:release
24h/day ¦ DHW release¦ Time program4/ DHW
DHW release -
5085 F Excess heat draw
Off ¦ On
On. -
5090 F With buffer
No ¦ Yes
No -
5092 F With primary controller / system pump
No ¦ Yes
No -
5093 F With solar integration
No ¦ Yes
Yes -
5101 F Pump speed min 40 0 100 %
5102 F Pump speed max 100 0 100 %
6)
57/258