Signal quality
During installation make sure that there is a good signal strength of > -73 dBm.
If the "Q" LED is lit permanently, the signal quality is good. For more detailed information,
refer to the section "LED display (Page28)".
Avoid large metallic objects in the immediate vicinity.
6.5 Grounding
Grounding for wall mounting
The device is grounded by the xing screw via the unpainted eyelet, position see section "Device
view (Page22)".
In addition to grounding via the xing screw, you can also ground the device using the
terminal block. The terminal is identied by the following symbol for the functional ground
, position see section "Terminals (Page27)". Connect the terminal of the device with as
short a cable as possible ≤ 150mm and with the required cross-sectional area to a grounded
part of the system.
If the device is mounted on a non-conductive base, grounding must be connected either via
the functional ground on the terminal block or via a grounding cable.
The grounding cable is not supplied with the device. Connect the paint-free surface of the
device to the nearest grounding point using the grounding cable.
Grounding when installing on a DIN rail / S7 mounting rail
The device is grounded via the rear of the device.
You can also ground the device via the terminal block. The terminal is identied by the
following symbol for the functional ground , position see section "Terminals (Page27)".
Connect the terminal of the device with as short a cable as possible ≤ 150mm and with the
required cross-sectional area to a grounded part of the system.
6.6 Digital input/output
The digital input and output are connected using a 2-pin plug-in terminal block in each case. Two
terminal blocks ship with the device.
NOTICE
Damage due to voltage being too high or too low
The voltage at the digital input/output must not exceed 30 VDC and not fall below -30 VDC,
otherwise the digital input/output will be destroyed.