Siemens SENTRON 3WL10
272 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting circular conductor terminals 4x240mm² on the guide frame
The circular conductor terminals 4x240mm² are provided unmounted with the guide frame.
Screw the circular conductor terminals 4x240mm² to the rear terminals for main circuit
connection. Pay attention to the prescribed positioning on the right or left on each terminal
for main circuit connection.
You will 󹪝nd more information in the relevant Operating Instructions (see Chapter Product-
speci󹪝c information (Page9)).
Connection and commissioning
5.2Mounting and connecting the device
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
160 Equipment Manual, 10/2023, L1V30499596002-03