Functions
6.4 Modbus TCP connection
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01
69
6.4.4.3 Bluetooth communication parameters
Regis-
ter
Lengt
h
Designation Format Value range De-
fault
Ac-
cess
POC
1000
5ST3
COM
5SL6
COM
5SV6
COM
3NA
COM
768
1
Bluetooth switch
on/off or reset
U16
1 = BLE switch on
2 = BLE switch off
3 = Passkey reset
CMD
x
-
-
-
-
769
1
Bluetooth Status
U16
0 = inactive
1 = connectable
2 = connected
R
x
-
-
-
-
770
1
Bluetooth trans-
mit power in dBm
S16
-18 .... 4
2
RW
x
-
-
-
-
771
3
Bluetooth device
address
U8[6]
R
x
-
-
-
-
774
2
Bluetooth Passkey
U32
000000 ... 999999
RW
x
-
-
-
-
6.4.4.4 Communication parameter radio
Regis-
ter
Lengt
h
Designation Format Value range Default Ac-
cess
POC
1000
5ST3
COM
5SL6
COM
5SV6
COM
3NA
COM
1042
2
Date/time (UTC)
U32
UNIX_TS since
01.01.1970
01.01.2000
at 00:00:00
RW
x
-
-
-
-
1026,
1027,
...
1049
1
Pairing status of
the terminal de-
vices 1 ... 24
U16
0 = Infor-
mation not
available
(MAC/Installati
on code miss-
ing)
1 = Pairing
running
2 = Pairing
completed
3 = Pairing
unsuccessful
5 = Pairing
timeout
9 = Remove
running
11 = Remove
timeout
R
x
-
-
-
-
1050
1
Transmit power in
dBm
S16
-18 ... 2
0
RW
x
x
x
x
x
1051,
1052,
...
1074
1
Device status of
the terminal de-
vices 1 ... 24
U16
0 = IDLE (no
terminal
device paired)
1 = Offline
2 = Connect
3 = Connected
R
x
-
-
-
-

Table of Contents