6.4 Modbus TCP connection
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01
71
Regis-
ter
Length Designation For
mat
Value range Unit Ac-
cess
POC
1000
5ST3
COM
5SL6
COM
5SV6
COM
3NA
COM
3102
4
Imported reactive
energy
FP64
Varh
R
-
-
x
x
-
3106
4
Exported reactive
energy
FP64
Varh
R
-
-
x
x
-
3110
1
Status of the
mounted circuit
protection devices
U16
0 = Status un-
known
1 = Breaker off,
without trip-
ping operation
2 = Breaker on
3 = Breaker
tripped
4 = Breaker
tripped, but
level on/blocked
R
-
x
-
-
-
6.4.4.7 Measurement settings
Reg-
ister
Length Designation For-
mat
Value
range
Default Unit Ac-
cess
POC
1000
5ST3
COM
5SL6
COM
5SV6
COM
3NA
COM
3586
2
Averaging peri-
od temperature
U32
3600 …
86400
21600
sec
RW
-
x
x
x
x
3588
1
Activating the
temperature
alarm
U16
0 = Off
1 = On
1
-
RW
-
x
x
x
x
3589
2
Limit values for
the temperature
alarm
FP32
20 … 110
105
°C
RW
-
x
x
x
x
3591
2
Hysteresis of the
temperature
alarm
FP32
0 … 10
10
%
RW
-
x
x
x
x
3597
1
Averaging peri-
od current
U16
3 … 3600
10
sec
RW
-
-
x
x
x
3598
1
Switching
Alarm1 on and
off for upper
current violation
U16
0 = Off
1 = On
1
RW
-
-
x
x
x
3599
2
Limit value of
upper current
violation for
Alarm1 in % of
In
FP32
0 … 150
80
%
RW
-
-
x
x
x
3601
2
Hysteresis for
upper current
violation Alarm1
FP32
0 … 10
5
%
RW
-
-
x
x
x
3607
1
Switching
Alarm2 on and
off for upper
current violation
U16
0 = Off
1 = On
0
RW
-
-
x
x
x