6.4 Modbus TCP connection
Circuit protection devices with communication and metering function
74 System Manual, 06/2021, L1V30827018B-01
6.4.4.8 Diagnostic information
Reg-
ister
Len
gth
Designation For-
mat
Value range Default Unit Ac-
cess
POC
1000
5ST3
COM
5SL6
COM
5SV6
COM
3NA
COM
2560
2
Alarms status
U32
See table
Alarms sta-
tus details
below.
R
x
x
x
x
x
2562
4
Operating
hours with load
current
FP64
sec
R
-
-
x
x
x
2566
1
Switching the
operating hours
violation with
load current
alarm on and
off
U16
0 = Off
1 = On
0
RW
-
-
x
x
x
2567
1
Minimal over-
load current
based on I
n,
from the point
at which the
operating hours
counter is ac-
tive
U16
5…90
70
%
RW
-
-
x
x
x
2568
4
Limit value of
the operating
hours alarm
with load cur-
rent
FP64
60 ...
360,000,00
0
8640000
sec
RW
-
-
x
x
x
2578
4
Total operating
hours (with and
without load
current)
FP64
sec
R
x
x
x
x
x
2582
1
Switching the
operating hours
violation alarm
on and off
U16
0 = Off
1 = On
0
RW
x
x
x
x
x
2583
4
Operating
hours limit
value
FP64
60 …
864000000
158000000
sec
RW
x
x
x
x
x
2593
2
Number of
mechanical
operating cy-
cles
FP32
R
-
x
x
x
-
2595
1
Switching the
mechanical
operating cy-
cles alarm on
and off
U16
0 = Off
1 = On
0
RW
-
x
x
x
-
2596
2
Mechanical
operating cy-
cles limit value
FP32
0 … 10000
1000
RW
-
x
x
x
-
2602
2
Number of
tripping opera-
tions
FP32
R
-
x
x
x
-